DZ47-125 Miniature Circuit Breaker
Contact:
1. Application
DZ47-125 is such features as delicate appearance, light weight, excellent andreliable performance, high breaking capacity, rapid tripping and mounted byrail. Its enclosure and components adopts high fire-retarding andshock-resistance plastic of long durability. It mainly servesfor protecting thecircuits of AC 50Hz, 230V of single pole, 400V of two poles or three or four polesfrom overload or short-circuit, and also for unfrequent making and breakingelectrical apparatus and lighting circuit.It conforms with the standards ofIEC60947-2.
2. MainTechnical Parameter
Type |
||
Pole |
1P |
2P,3P,4P |
Rated current (A) |
63,80,100,125 |
|
Rated voltage (V) |
230 |
400 |
Ambient temperature |
-5oC~+40oC |
|
Type of instantaneous release |
C,D |
|
Rated short circuit breaking capacity Icn(kA) |
6 |
3. Theover-current protection property
Ambient Temperature |
Initial Status |
Test Current |
Expected Result |
Expected Result |
NOte |
40±2oC |
Cold position |
1.05In(In≤63A) |
t≤1h |
Non-release |
- |
Cold position |
1.05In (In[63A) |
t≤2h |
Non-release |
- |
|
Carried out immedi-ately after previous test |
1.30In(In≤63A) |
t < 1h |
Release |
Current smoothlyrises to specified value within 5s |
|
1.30In (In>63A) |
t < 2h |
Release |
|||
-5~+40oC |
Cold position |
8.00In |
t≤0.2s |
Non-release |
- |
Cold position |
12.00In |
t< 0.2s |
Non-release |
- |
4.Applicable conducting wire
Rated current(A) |
Nominal cross section of wire mm2 |
63A |
16 |
80A |
25 |
100A |
35 |