ZN63A-12(VS1)Type lndoor High Voltage Vacuum Circuit Breaker
Contact:
Main application
ZN63A-12 (VS1) type indoor high voltage vacuum circuit breaker (hereinafter referred to as circuit breaker) is used for indoor high voltage switch equipment of power system, as a protection and control unit of network equipment, industrial and mining enterprises power equipment, suitable for the place of frequent operation at rated working current or many times of breaking short-circuit current place. The circuit breaker uses the integrated design of actuator and the circuit breaker body, not only can be used as a fixed install unit, also can be equipped with special chassis, hand car unit.
The use of environmental conditions
1. The environment temperature: upper limit+40℃, lower limit -15℃ (allow storage at -30℃);
2. Altitude: no more than 2000m;
3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%;
4. Saturated steam pressure: daily no larger than 2.2×10-3Mpa, monthly average is not greater than 1.8×10-3Mpa;
5. Earthquake intensity does not exceed 8 degrees;
6. No fire, explosion, pollution, chemical corrosion and severe vibration place;
Technical Parameter
Item |
Unit |
Parameter |
|||||||
Parameters of voltage, current, life | |||||||||
Rated voltage |
kV |
12 |
|||||||
Rated short time power frequency withstand voltage(1 min) |
kV |
42 |
|||||||
Rated lightning impulse withstand voltage (Peak) |
kV |
75 |
|||||||
Rated frequency |
Hz |
50 |
|||||||
Rated current |
A |
630 1250 |
1250 1600 2000 2500 |
1250 1600 2000 2500 3150 4000 |
4000 5000 |
||||
Rated short-circuit breaking current |
kA |
20 |
25 |
31.5 |
40 |
50 |
|||
Rated short-time withstand current(RMS) |
kA |
20 |
25 |
31.5 |
40 |
50 |
|||
Rated peak withstand current |
kA |
50 |
63 |
80 |
100 |
125 |
|||
Rated short-circuit closing current |
kA |
50 |
63 |
80 |
100 |
125 |
|||
Rated single/back-to-back capacitor bank breaking current |
A |
630/400 |
|||||||
Rated short-circuit current duration |
S |
4 |
|||||||
Rated short-circuit breaking times |
times |
50 |
30 |
||||||
Rated operating sequence |
O-t-CO-180s-CO rated short-circuit breaking current less than 31.5kA, t=0.3s rated short-circuit breaking current 40kA, t=180s |
||||||||
The main galvanic circle resistance |
µΩ |
≤50(less than 1250A); ≤40(less than 1600~2000A); ≤30(more than 2500A) |
|||||||
Rated operation voltage |
≌220/110 |
||||||||
Mechanical life |
times |
≥10000 |
|||||||
Mechanical property parameters | |||||||||
Open clearance between contacts |
mm |
11+1 |
|||||||
Overtravel |
mm |
3.0+0.5 |
|||||||
Contact closing bounce time |
ms |
2 |
3 |
||||||
Three-phase, switching in different period |
ms |
≤2 |
|||||||
Average opening speed |
m/s |
0.9~1.3 |
|||||||
Average closing speed |
m/s |
0.5~0.8 |
|||||||
Opening time (rated voltage) |
ms |
≤50 |
|||||||
Closing time (rated voltage) |
ms |
≤70 |