The main function of KYN28 switch cabinet is to open and close, control and protect electrical equipment in the process of power generation, transmission, distribution and electric energy conversion.  The components in the switch cabinet mainly include circuit breaker, disconnecting switch, load switch, operating mechanism, mutual inductor and various protective devices.  There are many classification methods of switchgear, such as the circuit breaker installation can be divided into moving switchgear and fixed switchgear;  Or according to the different structure of the cabinet, it can be divided into open switch cabinet, metal closed switch cabinet, and metal closed armored switch cabinet;  According to the different voltage levels can be divided into high voltage switchgear, medium voltage switchgear and low voltage switchgear.  Mainly applicable to power plants, substations, petrochemical, metallurgical steel rolling, light industry textile, factories and mining enterprises and residential areas, high-rise buildings and other different occasions.


Contact:

  • 电话
  • qq
  • sns03
  • sns01
  • skype
  • 播放器
  • sns02

Product Detail

Product Tags

The main function of switch cabinet is to open and close, control and protect electrical equipment in the process of power generation, transmission, distribution and electric energy conversion.  The components in the switch cabinet mainly include circuit breaker, disconnecting switch, load switch, operating mechanism, mutual inductor and various protective devices.  There are many classification methods of switchgear, such as the circuit breaker installation can be divided into moving switchgear and fixed switchgear;  Or according to the different structure of the cabinet, it can be divided into open switch cabinet, metal closed switch cabinet, and metal closed armored switch cabinet;  According to the different voltage levels can be divided into high voltage switchgear, medium voltage switchgear and low voltage switchgear.  Mainly applicable to power plants, substations, petrochemical, metallurgical steel rolling, light industry textile, factories and mining enterprises and residential areas, high-rise buildings and other different occasions.

General

1.    Ratings: system voltage 3.6kV, 7.2KV, 12KV, rated current up to 4000A, AC three phase 50/60HZ.

2.    Application: mainly applicable in the power plant, substation, mineral enterprise to receive and distribute power with the functions of controlling, protecting and monitoring. It also can be used in places where the frequently operations are inneed.

3.    Standard: IEC62271-200

Working Conditions

1. Ambient air temperature: -15℃~+40℃.

2.    Altitude: ≤1000m.

3.    Relative humidity : Daily average≤95%, daily averange of vapour pressure≤2.2kpa.

4.    Earthquake intensity: ≤magnitude 8.

5.    Applicable in the places without corrosive and flammable gas and water vapor.

6.    Used in place without frequently intense vibrant.

Note: Customized products are available

Main technical parameter

No. Item Unit

Data

1

Rated voltage

kV

12

2

Rated current Load break switchgear

A

630

Combined switchgear

A

125

3

Rated short-circuit breaking current

kA

31.5

4

Rated active on-load breaking current

A

630

5

Rated short-time withstands current

kA

20

6

Rated withstands current(Peak)

kA

50

7

Rated power frequency voltage withstands inter-phase, to earth and to the open contact

kV

42/48

8

Thundering withstands voltage inter-phase, to earth and to the open contact

kV

75/85

9

Mechanical life

times

10000

10

Rated take-over current

A

3150

11

Operating mode

Manual or automatic

12

Protection level

Ip2X

未标题-3

Outline size

Height(B)

2300(2200)

Width(A)

Rated current of branch bus≤1250A,

heat stable current≤40KA

800(650)

Rated current of branch bus≥1600A

1000

Depth(C)

Cable Incoming and outgoing feeder

1500

Overheaded incoming and outgoing feeder

1660

未标题-2

Height(B)

Width(A0

L1

L2

L3

L4

800

1500 cable

530

630

150

490

800

1660 aerial

530

630

310

650

1000

1500 cable

730

830

150

490

1000

1660 aerial

730

830

310

650