HGL-63-3150A series Load-isolation switch
Contact:
Application
The switch is used for overload insulation under AC 50/60Hz, rated voltage 660V rated current 3150A
Service environment
1,HGL load-isolation switch can operate under the following conditions
2.Altitude not more than 2000m;
3.The range of ambient temperature is from 5℃to 40℃;
4.Relative humidity not more than 95%;
5、The environment without any explosive medium.
6.The environment without any rain or snow attacking.
If the product is expected to be used in the environment where temperature is over +40′℃ or below -5℃-45℃,user’s shall tell it to the
manufacturer.
Conventional Thermal current(A) |
63A |
100A |
160A |
250A |
||||||
Rated current In(A) |
40 |
63 |
80 |
100 |
125 |
160 |
200 |
5000 |
||
Rated insulation voltage Ui (V) (installation type IV) |
690 |
690 |
690 |
690 |
690 |
690 |
690 |
690 |
||
Dielectric strength(V) |
5000 |
5000 |
5000 |
5000 |
5000 |
5000 |
5000 |
5000 |
||
Rated surge-resistant voltage Uimp KV(installed category IV) |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
||
Rated working current le(A) |
380V |
AC-21B |
40 |
63 |
80 |
80 |
125 |
160 |
200 |
200 |
AC-22B |
40 |
63 |
80 |
80 |
125 |
160 |
200 |
250 |
||
AC-23B |
40 |
50 |
80 |
80 |
125 |
160 |
200 |
250 |
||
660V |
AC-21B |
40 |
50 |
80 |
80 |
125 |
160 |
200 |
250 |
|
AC-22B |
32 |
32 |
50 |
50 |
125 |
160 |
160 |
160 |
||
AC-23B |
25 |
25 |
40 |
40 |
80 |
80 |
100 |
125 |
||
Motor power P (kW) | 380V |
19.5 |
25 |
40 |
40 |
63 |
80 |
100 |
132 |
|
660V |
22 |
22 |
33 |
33 |
75 |
75 |
90 |
110 |
||
Rated short-time withstand current Icw (kA Rms)0.1s/1s |
2 |
2 |
2 |
2 |
8 |
8 |
12 |
12 |
||
Rated breaking capability Icn(A Rms)AC23 380V |
320 |
504 |
640 |
800 |
1000 |
1000 |
1600 |
1600 |
||
Rated making capability Icm(A Rms)AC23 380V |
400 |
630 |
800 |
1000 |
1250 |
1600 |
2000 |
2500 |
||
Rated short-current making capability Icm(kA peak value) |
2.84 |
2.84 |
2.84 |
2.84 |
13.6 |
13.6 |
17 |
17 |
||
Mechanical durability 380V |
1700 |
1700 |
1700 |
1700 |
1400 |
1400 |
1400 |
1400 |
||
Electrical curability 380V |
300 |
300 |
300 |
300 |
200 |
200 |
200 |
200 |
||
Operation moment(Nm) |
1.2 |
1.2 |
1.2 |
1.2 |
6.5 |
6.5 |
10 |
10 |
Conventional Thermal current(A) |
630A |
1600A |
3150A |
|||||||||
Rated current In(A) |
315 |
400 |
500 |
630 |
1000 |
1250 |
1600 |
2000 |
2500 |
3150 |
||
Rated insulation voltage Ui (V) (installation type IV) |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
||
Dielectric strength(V) |
8000 |
8000 |
8000 |
8000 |
10000 |
10000 |
10000 |
10000 |
10000 |
10000 |
||
Rated surge-resistant voltage Uimp KV(installed category IV) |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
||
Rated working current le(A) |
380V |
AC-21B |
315 |
400 |
500 |
630 |
1000 |
1250 |
1600 |
2000 |
2500 |
3150 |
AC-22B |
315 |
400 |
500 |
630 |
1000 |
1250 |
1600 |
2000 |
2500 |
3150 |
||
AC-23B |
315 |
400 |
500 |
630 |
||||||||
660V |
AC-21B |
315 |
400 |
400 |
500 |
1000 |
1000 |
1600 |
2000 |
2500 |
2500 |
|
AC-22B |
315 |
315 |
315 |
315 |
800 |
800 |
800 |
1000 |
1250 |
1600 |
||
AC-23B |
||||||||||||
Motor power P (kW) | 380V |
160 |
220 |
280 |
315 |
560 |
560 |
560 |
710 |
710 |
710 |
|
660V |
185 |
185 |
185 |
185 |
475 |
475 |
475 |
750 |
750 |
750 |
||
Rated short-time withstand current Icw (kA Rms)0.1s/1s |
25 |
25 |
25 |
25 |
50 |
50 |
50 |
50 |
50 |
50 |
||
Rated breaking capability Icn(A Rms)AC23 380V |
2520 |
3200 |
4000 |
5040 |
3000 |
3750 |
4800 |
6000 |
7500 |
9450 |
||
Rated making capability Icm(A Rms)AC23 380V |
3150 |
4000 |
5000 |
6300 |
3000 |
3750 |
4800 |
6000 |
7500 |
9450 |
||
Rated short-current making capability Icm(kA peak value) |
40 |
40 |
40 |
40 |
70 |
70 |
70 |
105 |
105 |
105 |
||
Mechanical durability 380V |
800 |
800 |
800 |
800 |
500 |
500 |
500 |
300 |
300 |
300 |
||
Electrical curability 380V |
200 |
200 |
200 |
200 |
100 |
100 |
100 |
100 |
100 |
100 |
||
Operation moment(Nm) |
14.5 |
14.5 |
14.5 |
14.5 |
37 |
37 |
60 |
60 |
60 |
60 |