JDX(X)(F)18-3,6,10 RZL10 Series Voltage Transformer
Contact:
Summary
The voltage transform is the type of cast resin insulation and full enclosed, used for electric energy metering, voltage control and relay protection in the power systems of rated voltage 3kV, 6kV, and 10kV or below. The products are in accordance with IEC 60044 and GB1207-2006 Voltage Transformer.
Technical parameter
- Technical data form
- Partial dischanage is in line with GB1207-2006 voltage transformer
- Anti-polluction class:see fig
Technical Parameter
Type |
Rated Voltage Ratio(V) |
Rated output(VA) |
Ultimate Output(VA) |
Rated Insulation Level(kV) |
|||
0.2 |
0.5 |
1 |
6P |
||||
JDZ8-3 RZL10 |
300/100 |
15 |
30 |
60 |
500 |
3.6/25/40 |
|
JDZ8-3 RZL10 |
6000/100 |
7.2/32/60 |
|||||
JDZ8-3 RZL10 |
10000/100 |
12/42/75 |
|||||
JDZ18-3 |
3000/100/100 |
10 |
10 |
30 |
2*250 |
3.6/25/40 |
|
JDZ18-6 |
6000/100/100 |
7.2/32/60 |
|||||
JDZ18-10 |
10000/100/100 |
12/42/75 |
|||||
JDZ18-3 RZL10 |
3000/√3/100/ √3/10013 |
15 |
30 |
100 |
200 |
3.6/25/40 |
|
JDZ18-6 RZL10 |
6000/√3/100/ √3/100/3 |
7.2/25/40 |
|||||
JDZ18-10 RZL10 |
10000/√3/100/ √3/100/3 |
12/42/75 |
|||||
JDZF18-3 |
3000/√3/100/ √3/100/√3/100/3 |
10 |
10 |
60 |
200 |
3.6/25/40 |
|
JDZF18-6 |
6000/√3/100/ √3/100/√3/100/3 |
7.2/32/60 |
|||||
JDZF18-10 |
10000/√3/100/ √3/100/√3/100/3 |
12/42/75 |