RM6-12/24 Gas Insulated Ring Main Unit Switchgear adopts modular design,which fits the requirement of end user or network node by relying on perfectcombination of fixed and flexible expansion. It also meets the demand of various distribution switching stations, box-type substation and cable branch boxes. It has characteristics of compact structure, safe, reliable, long life and free maintenance. The switchgear includes an air tank welded by 3.0mm stainless steel, all live parts and switches are placed in it. Routine test shall be carried out for all elements/modules before the product leaves the factory. These elements/modules can be installed after delivery, and any special tool is not required.


Contact:

  • 电话
  • qq
  • sns03
  • sns01
  • skype
  • 播放器
  • sns02

Product Detail

Product Tags

Outline

RM6-12/24 Gas Insulated Ring Main Unit Switchgear adopts modular design,which fits the requirement of end user or network node by relying on perfectcombination of fixed and flexible expansion. It also meets the demand of various distribution switching stations, box-type substation and cable branch boxes. It has characteristics of compact structure, safe, reliable, long life and free maintenance. The switchgear includes an air tank welded by 3.0mm stainless steel, all live parts and switches are placed in it. Routine test shall be carried out for all elements/modules before the product leaves the factory. These elements/modules can be installed after delivery, and any special tool is not required.

Available module

·C Load break switch module

·De Cable connection module with earthing switch

·D Cable connection module without earthing switch

·F Load switch-fuse-combination unit module

·V Vacuum circuit breaker

·Be Bus ground module

M Meter module

·SL Bus section switch module(load switch)

*Sv Bus section switch module (vacuum circuit breaker)

Structural drawing of switchgear

1.Ring

2.Voltage indicator

3.Cable failure indictor

4.Pressure indicaton

5.Observation window for lower door

6.Analog circuit diagram

7.Integrated protection

8.Blown fuse indicator

9.Padlock device on the panel

10.Cover plate of cable chamber

11.Key lock(accessory)

12.Energy storage handle hole of circuit breaker

13.Load break switch handle hole(F unit energy storage)

14.Earthing switch handle hole

15.Isolating switch handle hole

16.Opening button(knob)

17.Closing button(knob)

18.Handle of cover plate of cable plate

19.Fuse room

Technical Parameter

S/N

Name

Unit

Parameter

Load switch cabinet

Combined switchgear

Circuit breaker cabinet

1

Rated voltage

kV

12/24

2

Rated current

A

630

125

630/1250

3

Rated short-time withstand current

kA/s

20/3,25/2

/

20/4,25/4,31.5/4

4

Rated peak withstand current

kA

50,63

/

50,63,80

5

Rated short-circuit breaking current

kA

/

31.5

20,25,31.5

6

Rated short-circuit closing current

kA

50,63

80

50,63,80

7

Rated transfer current

A

630

1700

/

8

Rated closed loop breaking current

A

100

/

/

9

Full capacity breaking times

times

5000

/

30

10

Mechanical life

times

5000

10000

11

1min power frequency withstand voltage/phase to phase, to earth

kV

42/50

12

1min power frequency withstand voltage/Isolation fracture

kV

48/58

13

Rated lighting impulse withstand voltage/phase to phase, to earth

kV

75/125

14

Rated lighting impulse withstand voltage/Isolation fracture

kV

85/125

15

Two circuit 1 min power frequency withstand voltage

kV

2