< img src="https://mc.yandex.ru/watch/85166581" style="position:absolute; left:-9999px;" alt="" />

XGN15-12 Package High voltage switchgear

Short Description:

The main function of XGN15-12 switch cabinet is to open and close, control and protect electrical equipment in the process of power generation, transmission, distribution and electric energy conversion.  The components in the switch cabinet mainly include circuit breaker, disconnecting switch, load switch, operating mechanism, mutual inductor and various protective devices.  There are many classification methods of switchgear, such as the circuit breaker installation can be divided into moving switchgear and fixed switchgear;  Or according to the different structure of the cabinet, it can be divided into open switch cabinet, metal closed switch cabinet, and metal closed armored switch cabinet;  According to the different voltage levels can be divided into high voltage switchgear, medium voltage switchgear and low voltage switchgear.  Mainly applicable to power plants, substations, petrochemical, metallurgical steel rolling, light industry textile, factories and mining enterprises and residential areas, high-rise buildings and other different occasions.


Contact:

  • 电话
  • qq
  • sns03
  • sns01
  • skype
  • 播放器
  • sns02

Product Detail

Product Tags

The main function of switch cabinet is to open and close, control and protect electrical equipment in the process of power generation, transmission, distribution and electric energy conversion.  The components in the switch cabinet mainly include circuit breaker, disconnecting switch, load switch, operating mechanism, mutual inductor and various protective devices.  There are many classification methods of switchgear, such as the circuit breaker installation can be divided into moving switchgear and fixed switchgear;  Or according to the different structure of the cabinet, it can be divided into open switch cabinet, metal closed switch cabinet, and metal closed armored switch cabinet;  According to the different voltage levels can be divided into high voltage switchgear, medium voltage switchgear and low voltage switchgear.  Mainly applicable to power plants, substations, petrochemical, metallurgical steel rolling, light industry textile, factories and mining enterprises and residential areas, high-rise buildings and other different occasions.

General

1.    Rating: Rated voltage 12KV, rated current reach to 630A.

2.    Application :mainly applicable in urban power grid construction and renovation project. industrial and mining enterprises.high-rise buildings and communal facilities .For power distribution .controlling and protection on electric equipment as the loop power supply unit or terminal equipment.It also can be installed in preloaded substation

3.    Feature: Use SF6 load switch and load switch-fuse combination as main switch. Equipped with vacuum load switch and spring operating mechanism which can be operated by hand or electric. Earthing switch and insulating switch are equipped with hand operating mechanism. With small volume and high security

4.    Standard: IEC60420

Working Conditions

1.    Ambient air temperature: -15℃~+40℃. Daily average temperature:≤35℃.

2.    Altitude: ≤1000m.

3.    Relative humidity : Daily average≤95% ,daily averange of vapour pressure≤2.2kpa Monthly average≤90%,monthly averange of vapour pressure≤1.8kpa.

4.    Earthquake intensity: ≤magnitude 8.

5.    Applicable in the places without corrosive and flammable gas.

Note: Customized products are available.

Structural feature

1.    SF6 load switch with insulated enclosure FLN36-13D and FLRN36-12D could be matched in switchgear.

2.    Compact design and easy operation.

3.    There is a pressure reliefing duct at the rear of the switchgear to protect the operator when a failure occurs in the switchgear.

4.    Allocation of the switchgear is changeable.

5.    Reliable interlocking at the different making status of the loading switch, earthing switch to ensure the reliable operation.

Main technical paramter

No.

Item

Unit

Data

Load switch cabinet

combined electric

appliance cabinet

(load switch-fuse)

1 Rated voltage

kV

12

12

2 Rated current of main bus

A

630

630

3 Rated current

A

630

125

4 Rated power

Hz

50

50

5 Rated short time withstands current/time

kV

20

6 Rated withstands current(Peak)

kA

50

31.5

7 Rated short circuit breaking current

kA

80

8 Rated short circuit closing current

kA

50

9 Rated active load breaking current

A

630

10 Rated closed loop breaking current

A

630

11 Rated cable charging breaking current

A

10

12 Earthing switch rated short time withstand current/time

kA

20

13 Earthing switch rated peak withstand current

kA

50

14 Rated shifting current

A

1700

15 Ratedinsulationlevel 1 min power frequency withstands voltage

kV

Between phases,

to earth 42

To open contact 48

lightening impulse withstands voltage

kV

Between phases,

to earth 75

To open contact 85

16 The main loop resistance

µΩ

≤300

≤300

17 Mechanical life(Load switch)

times

2000

2000

18 Mechanical life(Earthing switch)

times

2000

2000

19 Auxiliary loop 1 min power frequency withstand voltage

kV

2

2

20 protection level

IP3X

IP3X


  • Previous:
  • Next:

  • Related Products